Flexible Power Double Insulated

Home > Products > Building > Flexible Power Double Insulated

ZDU_Orange

SINGLE CORE DOUBLE INSULATED V90HT P.V.C. TO AS/NZS 5000.1

0.6/1KV VOLTAGE RATING

Applications:Fixed Power Applications, Switchboards, Busbars, Transformers
Conductor:Nominal 0.2mm bunched flexible Plain Copper Wire to AS1125
Insulation:Nitrile (NBR) Modified PVC to comply with AS3808 V90HT
Insulation Colour:White
Sheath:Nitrile (NBR) Modified PVC to comply with AS3808 V90HT
Sheath Colours:Orange, Black, other colours available by request
Packs:100 metres, bulk drum

Typical Properties – Standard: V90HT AS5000.1, AS1995

Specifications

CodeConductor
No. / Dia
(mm)
Nominal
Area
(mm²)
Insulation
Thickness
(mm)
Sheath
Thickness
(mm)
Electrical
Resistance
at 20°C
(ohm/km)
Nominal
O.D.
(mm)
Mass
(kg/100m)
ZDU132202**322/0.2101.01.41.919.114.42
ZDU151102**511/0.2161.01.41.2110.120.16
ZDU179202784/0.2251.21.40.7811.829.14
ZDU11121021120/0.2351.21.40.55413.138.96
ZDU11596021568/0.2501.41.40.38614.952.84
ZDU12212022240/0.2701.41.50.2721772.34
ZDU13021023040/0.2951.61.50.20619.396.18
ZDU13821023800/0.21201.61.60.16120.8117.86

 

Electrical Data

CodeCurrent
Rating* AMPS
2 Single Cores
Voltage Drop mV/Am at Max operating Temperature –
Single Phase
Voltage Drop mV/Am at Max operating Temperature – 
Three Phase
ZDU132202694.453.86
ZDU151102922.802.43
ZDU1792021251.781.54
ZDU11121021551.291.12
ZDU11596021850.960.83
ZDU12212022400.620.59
ZDU13021022950.510.44
ZDU13821023450.410.36

* Maximum operating temperature: 75°C in normal Use OR 105°C where not subject to, or protected from, mechanical damage (refer AS/NZS 3008.1.1:2009)
* AMP Ratings are to AS/NZS 3008. Unenclosed-Spaced at 40°C (in air), 25°C (in ground). Refer AS/NZS 3008 for derating factors – For Welding AMP Ratings refer to AS/NZS 1995.
* Tycab holds current independent compliance review report on PVC Cable compliance for GREEN STAR PVC Credit
** TUV AUTHORISED MARKING: TUV022088EA