Flat Fire Alarm


PrintE-mail

ACA N1155

EQUIVALENT TO ORDINARY DUTY




Applications: Evacuation Systems, Smoke Detectors and Alarms
Conductor:
Oxygen Free Plain Copper Wire to AS1125
Insulation:
RoHS Compliant 75°C PVC to AS3808
Core Colours: Red, White
Sheath: RoHS Compliant 75°C PVC to AS3808
Sheath Colour:
Red / Orange
Packs:
100, 500 metres

Code Cores Conductor
No. / Dia
(mm)
Nominal
Area
(mm²)
*AMP
Rating
Insulation
Thickness
(mm)
Sheath
Thickness
(mm)
Electrical
Resistance
at 20°C
(ohm/km)
Nominal
O.D.
(mm)
Mass
(kg/100m)
SWA22402*** 2 24/0.2 0.75 7.5 0.5 0.6 26 3.55x5.75 3.7
SWA2704 2 7/0.4 1 10 0.6 0.8 21.2 4.0x6.5 4.3
SWA2705 2 7/0.5 1.5 15 0.6 0.8 13.6 4.2x7.0 5.3

* AMP Ratings are to AS3008. Unenclosed-Spaced at 40°C. Refer to AS3008 for derating factors.