TYCAB DATA/INSTRUMENT BROCHURE

data.jpg


RS485 Overall Screen & Braid


PrintE-mail

ACA N1155 (AUSTEL APPROVED)





Applications: Data Communication, Low Capacitance
Conductor:
Tinned Copper Wire to AS1125
Insulation:
Data Grade Polyethylene
Core Colours: Pair 1: Black & White
Pair 2: Red & Green
Screen: Overall Aluminium / Polyester Laminate Tape Screen with a 7/0.2mm Tinned Copper Drain Wire
Braid: Tinned Coper Wire
Sheath: RoHS Compliant 75°C PVC to AS3808
Sheath Colour:
Grey
Packs:
100, 500 metres

Code Pairs Conductor
No. / Dia
(mm)
Nominal
Area
(mm²)
Insulation
Thickness
(mm)
Sheath
Thickness
(mm)
Electrical
Resistance
at 20°C
(ohm/km)
Capacitance
Wire to
Wire
(pF/m)
Capacitance
Wire to
Screen
(pF/m)
Impedence
OHMS
Nominal
O.D.
(mm)
Mass
(kg/100m)
DCK2702* 1 7/0.2 0.2 0.66 0.80 90.9 45 80 120 6.0 4.8
DCK4702 2 7/0.2 0.2 0.66 0.80 90.9 45 80 120 7.0 6.9

NOTE: (i) Extra Low Voltage - Not Suitable For Connection To Mains Power GPO