SINGLE CORE V90HT P.V.C. TO AS/NZS 5000.1

0.6/1KV VOLTAGE RATING

Applications:Power cable 0.6/1KV for fixed applications
Conductor:Nominal 0.2mm bunched flexible Plain Copper Wire to AS1125
Insulation:V90HT PVC to AS3808
Colours:Black, Red, Blue, White, Green/ Yellow
Packs:100 metres, bulk drum

Typical Properties – Standard: PVC Insulated Unprotected to AS5000.1

Specifications

CodeConductor
No. / Dia
(mm)
Nominal
Area
(mm²)
Insulation
Thickness
(mm)
Electrical
Resistance
at 20°C
(ohm/km)
Nominal
O.D.
(mm)
Mass
(kg/100m)
ZBD112802128/0.241.04.954.85.3
ZBD119202192/0.261.03.35.47.3
ZBD132202**322/0.2101.01.916.311.4
ZBD151102**511/0.2161.01.217.317.1
ZBD179202784/0.2251.20.788.830
ZBD11121021120/0.2351.20.55410.237.5
ZBD11596021568/0.2501.40.38611.951
ZBD12212022240/0.2701.40.2721471.5
ZBD13021023040/0.2951.60.2061697
ZBD13821023800/0.21201.60.16117.5119.1

 

Electrical Data

CodeCurrent
Rating* AMPS
2 Single Cores
Voltage Drop mV/Am at Max operating Temperature –
Single Phase
Voltage Drop mV/Am at Max operating Temperature – 
Three Phase
ZBD1128024011.209.71
ZBD119202517.506.49
ZBD132202694.453.86
ZBD151102922.802.43
ZBD1792021251.781.54
ZBD11121021551.291.12
ZBD11596021850.960.83
ZBD12212022400.620.59
ZBD13021022950.510.44
ZBD13821023450.410.36

* Maximum operating temperature: 75°C in normal Use OR 105°C where not subject to, or protected from, mechanical damage (refer AS/NZS 3008.1.1:2009)
* AMP Ratings are to AS/NZS 3008. Unenclosed-Spaced at 40°C (in air), 25°C (in ground). Refer AS/NZS 3008 for derating factors.
* Tycab holds current independent compliance review report on PVC Cable compliance for GREEN STAR PVC Credit
** TUV AUTHORISED MARKING: TUV022087EA

Colours