| Application: |
Building / Power Cable 0.6/1KV |
| Conductor: |
Plain Copper Wire to AS1125 |
| Insulation: |
V90HT PVC to AS3808 |
| Colours: | Black, Blue, Brown, Orange, Violet, Red, White, Grey, Green/Yellow - Stripes available by request |
| Packs: |
100, 500 metres |
Typical Properties - Standard: AS5000.1
| Code | Conductor No. / Dia (mm) |
Nominal Area (mm²) |
Insulation Thickness (mm) |
Electrical Resistance at 20°C (ohm/km) |
Nominal O.D. (mm) |
Mass (kg/100m) |
|
|---|---|---|---|---|---|---|---|
Electrical Data
| Code | Current Rating* AMPS 2 Single Cores |
Voltage Drop mV/Am at Max operating Temperature - Single Phase |
Voltage Drop mV/Am at Max operating Temperature - Three Phase |
|
BVD1108 |
5 | 125 | N/A |
| BVD11113 | 16 | 51.63 | 44.70 |
| BVD1705 | 21 | 33.03 | 28.60 |
| BVD17067 | 30 | 18.02 | 15.60 |
| BVD17085 | 40 | 11.22 | 9.71 |
| BVD17104 | 51 | 7.50 | 6.49 |
| BVD17135 | 69 | 4.45 | 3.86 |
| BVD17170 | 92 | 2.80 | 2.43 |
* AMP Ratings are to AS3008. Unenclosed-Spaced at 40°C. Refer AS3008 for derating factors.